1 x 16mm² – ZDXU151102


0.6/1KV R-E-110 Insulated, Nitrile Modified Sheath 110°c

Applications
Power: Switchboards, Busbars, Transformers.

Specification Sheet:
  Click to download specifications

16.0mmsq Plain Copper Wire. R-E-110 Insulated, V90HT Nitrile modified PVC Sheathed single core.
0.6/1KV to AS5000 with a flexible conductor.

Construction

Conductor: 511 strands of 0.2 mm Plain Annealed Copper to AS1125 drawn from Class 110A copper to AS1574.
Max. D.C. resistance at 20C : 1.21 ohms / klm.

Insulation: Coloured R-E-110 to AS3808
Nominal Diameter: 7.1 mm.
Nom. Wall Thickness: 1.0 mm.

Sheath: Coloured Nitrile modified P.V.C. type V90HT to AS3808
Nominal Diameter: 9.9 mm.
Nom. Wall Thickness: 1.4 mm.

Identification: Cable marked at intervals not exceeding 500mm – “TYCAB 2006 R-E-110 ELECTRIC CABLE 0.6/1KV”

Amp rating @ 30°C: 92

 Electrical characteristics
Voltage Drop Single Phase: 3.13
Voltage Drop Three Phase: 2.7

Reference Standards:
AS1125 Max. conductor Resistance
AS3808 INSULATION and sheath compound type.
AS5000 Construction to 0.6/1KV sheathed single core for fixed applications
AS3008 Power Amp Ratings, Voltage Drop, Derating Factors.