Specification Sheet:
Click to download specifications
120 mmsq Plain copper. R-E-110 Insulated,
V90HT Nitrile modified PVC sheathed single core.
0.6/1KV to AS5000.1 with a flexible conductor.
For Fixed Application.
Construction
Conductor: 3800 strands of 0.2 mm nom Plain Annealed Copper to AS1125 drawn from Class 110A copper to AS1574.
Max. D.C. resistance at 20C : 0.161 ohms / km.
Insulation: Coloured R-E-110 to AS3808
Nominal Diameter: 17.5 mm.
Nom. Wall Thickness: 1.6 mm.
Sheath: Coloured Nitrile modified P.V.C. type V90HT to AS3808.
Nominal Diameter: 20.8 mm.
Nom. Wall Thickness: 1.6 mm.
Identification: Cable marked at intervals not exceeding 500mm – “TYCAB 2012 R-E-110 ELECTRIC CABLE 0.6/1KV”
Amp rating @ 30°C: 345
Electrical characteristics
Voltage Drop Single Phase: 0.465
Voltage Drop Three Phase: 0.39
Reference Standards:
AS1125 Max. conductor Resistance
AS3808 INSULATION and sheath compound type.
AS5000 Construction to 0.6/1KV sheathed single core for fixed applications CABLE TESTS TO TABLE 5 AS APPLICABLE
AS3008 Power Amp Ratings, Voltage Drop, Derating Factors.