1 x 50mm² – ZDXU1159602


0.6/1KV R-E-110 Insulated, Nitrile Modified Sheath 110°c

Applications
Power: Switchboards, Busbars, Transformers.

Specification Sheet:
  Click to download specifications

50.0 mmsq Plain copper R-E-110 Insulated and V90HT.
Nitrile modified P.V.C sheathed single core 0.6/1KV to AS5000 with a FLEXIBLE conductor.

Construction

Conductor: strands of 0.2 mm nom Plain Annealed Copper to AS1125 drawn from Class 110A copper to AS1574.
Max. D.C. resistance at 20C : 0.386 ohms / klm.

Insulation: Coloured R-E-110 to AS3808
Nominal Diameter: 11.7 mm.
Nom. Wall Thickness: 1.2 mm.

Sheath: Coloured Nitrile modified P.V.C. type V90HT to AS3808
Nominal Diameter: 14.7 mm.
Nom. Wall Thickness: 1.4 mm.

Identification: Printed at intervals not exceeding 500 mm – “TYCAB 2006 R-E-110 ELECTRIC CABLE 0.6/1KV”

Amp rating @ 30°C: 185

Electrical characteristics
Voltage Drop Single Phase: 1.07
Voltage Drop Three Phase: 0.92

Reference Standards:
AS1125 Max. conductor Resistance
AS3808 INSULATION and sheath compound type.
AS5000 Construction to 0.6/1KV sheathed single core for fixed applications
AS3008 Power Amp Ratings, Voltage Drop, Derating Factors.