1 x 35mm² – ZDXU1112102


0.6/1KV R-E-110 Insulated, Nitrile Modified Sheath 110°c

Applications
Power: Switchboards, Busbars, Transformers.

Specification Sheet:
  Click to download specifications

35.0mmsq Plain Copper Wire.
R-E-110 Insulated, V90HT Nitrile modified PVC sheathed single core.
0.6/1KV to AS/NZS5000.1 with flexible conductor.
For Fixed Application.

Construction

Conductor: 1120 strands of 0.2 mm nominal Plain Annealed Copper to AS/NZS 1125 drawn from Class 110A copper to AS/NZS1574.
Max. D.C. resistance at 20C: 0.554 ohms / km.

Insulation: Coloured R-E-110 AS/NZS3808.
Nominal Diameter: 10.2 mm.
Nominal Wall Thickness: 1.2 mm.

Sheath: Coloured Nitrile modified P.V.C. type V90HT to AS/NZS3808.
Nominal Diameter: 13.1 mm.
Nominal Wall Thickness: 1.4 mm.

Identification: Cable marked at intervals not exceeding 500mm – “TYCAB 2014 R-E-110 ELECTRIC CABLE 0.6/1KV”

Amp rating @ 30°C: 155

Electrical characteristics
Voltage Drop Single Phase: 1.44
Voltage Drop Three Phase: 1.24

Reference Standards:
AS1125 Max. conductor Resistance
AS3808 INSULATION and sheath compound type.
AS5000 Construction to 0.6/1KV sheathed single core for fixed applications
AS3008 Power Amp Ratings, Voltage Drop, Derating Factors.