1 x 10mm² – ZDU132202


0.6/1KV PVC insulated, Nitrile Modified Sheath 105°c

Applications
Power: Switchboards, Busbars, Transformers.
Welding: Earth and Electrode Leads.
Automotive: Jumper Leads, Battery Charges.

Specification Sheet:
  Click to download specifications

10.0 mmsq Plain Copper Wire.
Nitrile modified V90HT PVC Insulated and Sheathed single core.
0.6/1KV to AS/NZS 5000.
For fixed application with flexible conductor.

Construction

Conductor: 322 strands of 0.2 mm nom Plain Annealed Copper to AS/NZS 1125 drawn from Class 110A copper to AS/NZS 1574.
Max. D.C. resistance at 20C: 1.91 ohms / km.

Insulation: Coloured Nitrile modified P.V.C. type V90HT to AS/NZS 3808.
Nominal Diameter: 6.2 mm.
Nominal Wall Thickness: 1.0 mm.

Sheath: Coloured Nitrile modified P.V.C. type V90HT to AS/NZS 3808.
Nominal Diameter: 9.1 mm.
Nominal Wall Thickness: 1.4 mm.

Identification: Embossed at intervals not exceeding 200mm – “TYCAB 10 mmsq 2000 V90HT ELECTRIC CABLE 0.6/1KV”

Amp rating @ 30°C: 69

Electrical characteristics
Voltage Drop Single Phase: 4.45
Voltage Drop Three Phase: 3.86

Reference Standards:
AS/NZS 1125 Max. conductor Resistance.
AS/NZS 3808 PVC compound type.
AS/NZS 5000 Construction to 0.6/1KV SHEATHED SINGLE CORE.
AS/NZS 3008 Power Amp Ratings, Voltage Drop, Derating Factors.