Specification Sheet:
Click to download specifications
4 Core 7/.1.04 (6 mm sq ) .plus 7/.67 (2.5 mmsq) Earth
P.C.W. V90 PVC insulated and 5V90 P.V.C. sheathed.
Circular Building Cable .450/750 volt to AS/NZS 5000.2 .
Oxygen Free Copper. RoHS Compliant.
Construction
Conductor:
PHASE: 7 strands of 1.04 mm Plain Annealed Copper to AS1125 drawn from Class 102 copper to AS1574.
Max. D.C. resistance at 20C : 3.08 ohms / km.
EARTH: 7 strands of 0.67 mm Plain Annealed Copper to AS1125 drawn from Class 102 copper to AS1574.
Max. D.C. resistance at 20C : 7.41 ohms / km.
Insulation:
ACTIVE & NEUTRAL: Coloured V90 to AS/NZS 3808.
Nominal Diameter: 4.8mm.
Nom. Wall Thickness: 0.8mm.
EARTH: Coloured V90 to AS/NZS 3808.
Nominal Diameter: 3.4mm.
Nom. Wall Thickness: 0.7mm.
Lay Up: 5 Cores laid up.
ACTIVE:
1. Red
2. White
3. Blue
NEUTRAL:
4. Black
EARTH:
5. Lt Green / Yellow
Around a polypropylene centre filler.
Sheath: Coloured P.V.C. type 5V90 to AS/NZS 3808.
Target Diameter: 15.1 mm.
Nom. Wall Thickness: 1.4 mm.
Identification: Printed on the sheath – TYCAB 2013 ELECTRIC CABLE V90 450/750V – BMM57104 4 x 6mmsq + 2.5mmsq E.