Specification Sheet:
Click to download specifications
3 Core Flat Twin and Earth 7/0.5 (1.5mmsq nom.). P.A.C.W.
V90HT P.V.C. Insulated and Non-Migratory 3V90 P.V.C. Sheathed.
Building cable 450/750 Volt to AS/NZS 5000.2.
Oxygen-Free Copper. RoHS compliant P.V.C.
Current Rating
Unenclosed in air: 18
Completely surrounded by thermal insulation: 9
Unenclosed Partially surrounded by insulation: 14
Electrical characteristics
Voltage Drop Single Phase mV/Am at 75°C Laid Flat: 33.03
Voltage Drop Three Phase mV/Am at 75°C Laid Flat: 28.6
Construction
Conductor: 7 strands of 0.5mm nom. Plain Annealed Copper to AS/NZS 1125 Class 2.
Max. D.C. resistance at 20C: 13.6 ohms / km.
Insulation:Coloured V90HT P.V.C. to AS/NZS 3808.
Nominal Diameter: 2.7 mm.
Nominal Wall Thickness: 0.6 mm.
Core Colours:
1. Red
2. Black
3. Lt. Green/Yellow
Laid parallel
Sheath: Coloured Non Migratory 3V90 P.V.C. to AS/NZS 3808. Flat configuration.
Nominal Dimensions: 4.6 x 9.9 mm.
Nominal Wall Thickness: 0.9 mm.
Identification:Printed on the sheath and metre marked – TYCAB 2016 V90 ELECTRIC CABLE 450/750V BED3705 1.5MMSQ T&E NON-MIG 001M >I<