3C x 6mm²+ 3E x 1.5mm²- VSD04/6.0


PCW X-90 Insulated

Applications
Suitable for use with VSD’s where RFI & EMI, protection is required
Suitable for fixed installations.
Rated voltage 0.6/1Kv

Specification Sheet:
  Click to download specifications

Phase Conductor 3 Core 84/0.3mm (6 mmsq)
Earth Conductor 3 Core 30/0.25 (1.5 mmsq)
P.C.W. X-90 (XLPE)
VSD Cable 0.6/1Kv to AS/NZS5000.1.
Oxygen-Free Copper. RoHS Compliant.

Construction

Conductor:

PHASE: 84 strands of 6 mm nom. Stranded Tinned Copper to AS1125 drawn from Class 5 Copper IEC60228
Max. D.C. resistance at 20C: < 3.4 / km.

EARTH: 30 strands of 1.5 mm nom. Stranded Tinned Copper to AS1125 drawn from Class 5 Copper IEC60228
Max. D.C. resistance at 20C: <13.7 ohms / km.

Insulation:

ACTIVE & NEUTRAL: Coloured X-90 to AS/NZS 3808.
Nominal Diameter: 3.17 mm.
Nominal Wall Thickness: 0.7 mm.

EARTH: Coloured X-90 to AS/NZS 3808.
Nominal Diameter: 1.57 mm.
Nominal Wall Thickness: 0.5 mm.

Lay Up: 4 Cores laid up.

ACTIVE:

1. Red
2. White
3. Blue

EARTH:

4. Lt Green / Yellow x 3

First Shield:
Material AL/pet tape
Construction Overall & helically wrapping, 100% coverage

Second Shield
Material Tinned Copper Wire
Construction 24*8*0.16mm, braiding coverage 85%

Jacket
Material Black 5V 90 PVC, UV Stabilized
Nominated External Target Diameter: 15.4 mm.
Nominal Wall Thickness: 1.8 mm.

Cable Weight 436kg/Km

Identification: Printed on the sheath – TYCAB (YEAR 2023) ELECTRIC CABLE 5V-90 0.6/1Kv – VSD04/6.0 3 x 6 mm2 + Earth 1.5 mm2