1 x 120mm² – ZBD1382102


0.6/1KV PVC insulated 105°c

Applications
Power Cable (Fixed Applications)

Specification Sheet:
  Click to download specifications

120 mm2 Plain copper V90HT PVC Insulated.
single-core 0.6/1kv to AS5000.1
For fixed application with flexible conductor.

Construction

Conductor: 3800 strands of 0.2 mm nom Plain Annealed Copper to AS1125 drawn from Class 110A copper to AS1574.
Max. D.C. resistance at 20C : 0.161 ohms / km.

Insulation: Coloured P.V.C. type V90HT to AS3808.
Nominal Diameter: 17.5 mm.
Nom. Wall Thickness: 1.6 mm.

Identification: Indented at intervals not exceeding 500mm – “TYCAB 120 MM2 2000 V90HT ELECTRIC CABLE 0.6/1KV”

Amp rating @ 30°C: 345

Electrical characteristics
Voltage Drop Single Phase: 0.41
Voltage Drop Three Phase: 0.359

Reference Standards:
AS1125 Max. conductor Resistance.
AS3808 PVC compound type.
AS5000 Construction to 0.6/1KV SINGLE CORE.
AS3008.1.2:2010 Power Amp Ratings (table 4), Voltage Drop, Derating Factors.