1 x 90mm² – ZBD1302102


0.6/1KV PVC insulated 105°c

Applications
Power Cable (Fixed Applications)

Specification Sheet:
  Click to download specifications

3024/.20 (95.0 mmsq) Plain Copper V90HT PVC Sheathed
0.6/1KV unprotected single-core to AS/NZS5000.1
For fixed application with flexible conductor.

Construction

Conductor: 3024 strands of 0.2 mm Plain Annealed Copper to AS/NZS 1125 drawn from Class 110A copper to AS/NZS 1574.
Max. D.C. resistance at 20C 0.206 ohms / km.

Insulation: Coloured P.V.C. type V90HT to AS/NZS 3808.
Nominal Diameter: 15.8mm.
Nominal Wall Thickness: 1.6mm.

Identification: Embossed at intervals not exceeding 200mm – “TYCAB 95mmsq 2000 V90HT ELECTRIC CABLE 0.6/1KV”

Amp rating @ 30°C: 295

Electrical characteristics
Voltage Drop Single Phase: 0.51
Voltage Drop Three Phase: 0.439

Reference Standards:
AS/NZS 1995: Max. Conductor Resistance.
AS/NZS 3808: PVC compound type.
AS/NZS 5000: Construction to 0.6/1KV UNPROTECTED type.
AS/NZS 3008: Power Amp Ratings TABLE 3, Voltage Drop, Derating Factors.