Specification Sheet:
Click to download specifications
120 mmsq Plain Copper Wire Nitrile modified V90HT PVC insulated and sheathed single core 0.6/1KV to AS/NZS 5000.1.
For fixed application with flexible conductor.
Construction
Conductor: 3800 strands of 0.2 mm nom Plain Annealed Copper to AS/NZS 1125 drawn from Class 110A copper to AS/NZS 1574.
Max. D.C. resistance at 20C: 0.161 ohms / km.
Insulation: Coloured Nitrile modified P.V.C. type V90HT to AS/NZS 3808.
Nominal Diameter: 17.5 mm.
Nominal Wall Thickness: 1.6 mm.
Sheath: Coloured Nitrile modified P.V.C. type V90HT to AS/NZS 3808.
Nominal Diameter: 20.8 mm.
Nominal Wall Thickness: 1.6 mm.
Identification: Embossed at intervals not exceeding 200mm “TYCAB 120 mmsq 2000 V90HT ELECTRIC CABLE 0.6/1KV”
Amp rating @ 30°C: 345
Electrical characteristics
Voltage Drop Single Phase: 0.41
Voltage Drop Three Phase: 0.359
Reference Standards:
AS/NZS 1125 Max. conductor Resistance.
AS/NZS 3808 PVC compound type.
AS/NZS 5000 Construction to 0.6/1KV SHEATHED SINGLE CORE.
AS/NZS 3008 Power Amp Ratings, Voltage Drop, Derating Factors.