2C + E x 4mm² – BED37085


Non-Migratory 3V90 Sheath 450/750V

Applications
Can be installed in contact with polystyrene and polyurethane.
Includes Caravans, Cold rooms, transportable buildings and in contact with polystyrene wall and roofing insulation materials.

Specification Sheet:
  Click to download specifications

3 Core Flat: Twin and Earth 2 x7/0.85 (4 mm2) plus 1 x 7/.67 (2.5mmsq) Earth
P.A.C.W. Non-Migratory P.V.C. Insulated and Sheathed.
Building Cable 450/750 volt to AS/NZS 5000.2.
Oxygen-Free Copper. RoHS Compliant.

Current Rating
Unenclosed in air: 35
Completely surrounded by thermal insulation: 17
Unenclosed Partially surrounded by insulation: 26

Electrical characteristics
Voltage Drop Single Phase mV/Am at 75°C Laid Flat: 10.59
Voltage Drop Three Phase mV/Am at 75°C Laid Flat: 9.71

Construction

Conductor:

PHASE: 7 strands of 0.85 mm Plain Annealed Copper to AS1125 drawn from Class 102 copper to AS1574.
Max. D.C. resistance at 20C: 4.61 ohms / km.

EARTH: 7 strands of 0.67 mm Plain Annealed Copper to AS1125 drawn From Class 102 copper to AS1574.
Max. D.C. resistance at 20C: 7.41 ohms / km.

Insulation:

ACTIVE & NEUTRAL: Coloured Non-Migratory P.V.C. to AS/NZS 3808.
Nominal Diameter: 4.2mm.
Nom. Wall Thickness: 0.8mm.

EARTH: Coloured V90. To AS/NZS 3808.
Nominal Diameter: 3.4mm.
Nom. Wall Thickness: 0.7mm.

Core Colours:
ACTIVE:
1. Red
NEUTRAL: 2. Black
EARTH: 3. Lt Green / Yellow (in centre)
Laid parallel.

Sheath: Coloured Non-Migratory P.V.C. to AS/NZS 3808. Flat configuration.
Nominal Dimensions: 6.4 x 14.8 mm.
Nom. Wall Thickness: 1.1 mm.

Identification: Printed on the sheath – TYCAB 2016 ELECTRIC CABLE V90 450/750V – BED37085 4MM2 T + 2.5MM2 E.