3 x 1.5mm² – BED3G05


Non-Migratory 3V90 Sheath 450/750V

Applications
Can be installed in contact with polystyrene and polyurethane.
Includes Caravans, Cold rooms, transportable buildings and in contact with polystyrene wall and roofing insulation materials.

Specification Sheet:
  Click to download specifications

3 Core Flat Twin and Earth 7/0.5 (1.5mmsq nom.). P.A.C.W.
Non-Migratory P.V.C. Insulated and Sheathed.
Building cable 450/750 Volt to AS/NZS 5000.2.
Oxygen-Free Copper. RoHS compliant.

Current Rating
Unenclosed in air: 18
Completely surrounded by thermal insulation: 9
Unenclosed Partially surrounded by insulation: 14

Electrical characteristics
Voltage Drop Single Phase mV/Am at 75°C Laid Flat: 33.03
Voltage Drop Three Phase mV/Am at 75°C Laid Flat: 28.6

Construction

Conductor: 7 strands of 0.5mm nom. Plain Annealed Copper to AS/NZS 1125 Class 2.
Max. D.C. resistance at 20C: 13.6 ohms / km.

Insulation: Coloured Non-Migratory V90 P.V.C. to AS/NZS 3808.
Nominal Diameter: 2.7 mm.
Nominal Wall Thickness: 0.6 mm.

Core Colours:
1. Red
2. White
3. Blue
Laid parallel

Sheath: Coloured Non-Migratory 3V90 P.V.C. to AS/NZS 3808. Flat configuration.
Nominal Dimensions: 4.6 x 9.9 mm.
Nominal Wall Thickness: 0.9 mm.

Identification: Printed on the sheath at maximum 500mm intervals and metre marked – TYCAB NON MIGRATORY 2016 ELECTRIC CABLE V90 450/750V – BED3G05 1.5MMSQ 3 CORE ACTIVE 001M >I<